Reseau Fast Ethernet Redundant Network

Your hosting includes a traffic of 50 mega


Aternating supply 230v and continuous supply 48v.

The alternating current of 230 V is helping by redundant UPS batteries, which have an autonomy of 30 minutes with complet charge.

The continuous current of 48 V is provided by undulators and batteries which have an autonomy of 1 hour with complet charge.

Two redundant electricity generators are on the site too, on top of these systems.

A generator has an autonomy of 72 hours.

AIR CONDITIONED
The hosting center is equipped with a double system of cooling conneted to the generators.

The system is designed to remove the heat of 250 W/m2 with an additional capacity of 20 % for the exterior sources.

The temperature is maintained to an average of 24°C, to a humidity included between 40 and 60%.

FIRE
The building is equipped with a system of double detection of fire (optical and detection of heat) coupled with a system of gaz put out.

The whole of this against fire system is answered to Europeen norms in force.

INTRUSION
The access to the site is only possible by appointment, accompagned by a technicien.

The rooms are equipped with against intrusion alarms, connected to a surveillance center.

All the alarms of the site (generators, electricity, A/C, against fire, temperature, humidity, leaks and intrusions) are connected to the controle center 24 hours a day.